Staticworx® EC Series ESD Rubber Flooring

ESD Rubber Tile Styles demonstrated.Staticworx® EC Rubber Series

The first ESD floor that is conductive, antistatic and capable of handling applications where special footwear is not an option. Staticworx® EC offers the only light colored, electrically conductive rubber flooring. Static generation less than 10 volts according to ESD STM 97.2 (tested with conductive shoes). Easy to maintain, never needs conductive wax; Resistant to chemicals and hot solder; Reduces explosion risk; Slip resistance in compliance with ADA guidelines; PVC and Phthalate free. EC Rubber is the recipient of the prestigious ESD Journal Seal of Approval for excellence and is Indoor Air Quality Certified.

Staticworx has the only Class 0 Certified ESD floorStaticworx has the only Class 0 Certified ESD floor.

Buildings Magazine list of the Top 81 Money Savings building products of 2010. Staticworx EC Rubber Staticworx EC rubber chosen by www.buildings.com Magazine as a Top Money-Saving Product.

ESD Journal Seal of ApprovalEC Rubber is the recipient of the prestigious ESD Journal Seal of Approval
and it's Indoor Air Quality Certified

Quick Links: Colors | Specs | ANSI Info. | Sustainability | Seam Weld | Master Spec (.doc)


Colors

Cantata EC Rubber sample

Cantata
Quick ship color

Presto EC Rubber Sample

Presto
Quick ship color

Largo EC Rubber Sample

Largo
Quick ship color

Staccato EC Rubber Sample

Staccato*
(Special order color.)

Click swatch
for larger view
---

Request
a sample >

Installation Solution!
EC ESD Rubber sheet flooring can be installed with instant-set, dry adhesive StaticFix > Learn more

---------

PVC free American made vinyl tile
Staticworx
EC Rubber Tile
is Phthalate Free
PVC Free

As colors cannot be assured to accurately appear on all computer monitors, please request a sample.

Download a pdf of this product's colors and specs Download a pdf of the color and specifications for this product.

Overview of Specifications

 

Download a pdf of this product's colors and specs Download a pdf of the color and specifications for this product.

Specifications

Staticworx® EC Rubber

Construction:

Two-layer, vulcanized conductive rubber with high quality natural and industrial rubber components.

Thickness:

2 mm

Total Weight:

N/A

Size:

24" x 24" tile and 4’ x 40' rolls

Static Generation Comparison Less than 10 Volts per ESD STM 97.2

< 20 volts when tested according to ESD STM 97.2

Abrasion Resistance:
(ASTM D 3389 H-18 wheel, 500gm load)

Taber abrasion test, ASTM D 3389, H-18 wheel, 500 gram load, 1000 cycles, gram weight loss not greater than 0.70

System Resistance

< 1.0 x 106

Staticworx® EC Rubber Flooring Is Ideal For:

  • R & D labs
  • air traffic control areas
  • computer rooms
  • electronics handling
  • wafer fabrication
  • medical electronics
  • clean rooms
  • data centers
  • electronics manufacturing
  • testing-repair areas
  • munitions and ordinance*
  • May be used in conjunction with dry adhesive

Staticworx EC Rubber on Access floor in data centerThe first rubber ESD flooring material that meets all the electrical parameters of ANSI/ESD S20.20-2007.

Standard ESD rubber flooring will not meet the recommended system resistance limits of ANSI/ESD S20.20-2007. Unfortunately, typical single layer rubber flooring usually provides an electrical resistance that is in the upper spectrum of the range commonly known as static dissipative. This creates a real dilemma for companies trying to stay current or ahead of increasingly demanding ESD standards. According to ANSI/ESD S20.20-2007, the recommended floor and footwear system resistance tested per ESD STM97.1 should measure less than 35 meg ohms (3.5X106). That isn't possible for single layer ESD rubber floors; single ply dissipative rubber lacks the inherent conductivity to meet this parameter.

How do most ESD rubber suppliers meet ANSI/ESD S20.20-2007?

Single ply rubber floors meet ANSI/ESD S20.20-2007 based upon low walking body voltage parameters. If a floor exhibits less than 100 volts of walking body voltage using controlled footwear that floor can theoretically claim compliance with ANSI/ESD S20.20-2007. However, meeting walking body voltage but not system resistance causes severe compliance issues for the quality department during routine certifications and plant audits. Walking body voltage is cumbersome and difficult to measure and monitor and require sophisticated expensive testing methods. It is much easier for owners to test and re-qualify their floors using resistance measuring equipment; anyone can perform resistance tests and the equipment is portable and inexpensive. Walking body voltage is measured using charge plate monitors and should always be evaluated using statistical analysis since there are a number of intervening variables. The Staticworx® EC Series was developed to harmonize with all recommended electrical parameters of ANSI/ESD S20.20-2007 and not just meet the requirements through a loop-hole like walking body voltage. With Staticworx® EC, there is no compromise.

Are you looking for static flooring for a command center, control room, E-9-1-1 dispatcher area or data center? Did you know that EC rubber prevents static in applications where people will be wearing standard shoes?

Vinyl interlocking floors generate static unless they are used with special conductive shoes. Rubber is the only static resistant flooring that works regardless of footwear. MIT testing rececently demonstrated that rubber is the only static resistant flooring that works regardless of footwear.

Will Staticworx® EC reduce walking body voltage on people?

Staticworx® EC will prevent walking body voltages above 10 volts when used in conjunction with controlled footwear - regardless of relative humidity.

Test results from MIT Lincoln Laboratories demonstrate that a static conductive rubber (not static dissipative) can significantly inhibit the accumulation of static electricity on people, regardless of footwear.

But, Staticworx® EC also prevents significant accumulation of static even in situations where grounded footwear is forgotten or not used. Ask us for the independent test reports about Staticworx® EC and take the time to read the study that lead to the development of the first fault tolerant ESD flooring material.

Two layer vulcanized construction combines the static control advantages of conductive flooring with ergonomic and safety advantages of rubber flooring.

  • Designed for class Zero ESD flooring applications.
  • Ideal electrical resistance. Resistance to ground is typically in the 100,000 – 1,000,000 ohm range.
  • Walking body voltage with heel straps is less than 10 volts at extremely low relative humidity.
  • Walking body voltage with typical footwear is < 0.5 kV
  • Available in tiles or sheet goods. 
  • Reduces noise from rolling as well as foot traffic.
  • PVC Free

Walking body voltage answersTypical static dissipative rubber usually has electrical properties at or above the upper limit of resistance recommended in ANSI/ESD S20.20-2007. Vulcanized construction of Staticworx® EC provides a perfect balance between conductivity and safety.

top
Request Your Free
Architectural Binder
Free static flooring samples
click here
ESD Vinyl
Tile Brochure
Ameriworx Brochure
Download PDF
StaticWorx
Rubber
Ameriworx Brochure
Download PDF
ESD Flooring Lifetime Product Warranty